How to Quickly Troubleshoot an Open Circuit in a Temperature-Sensing Cable

Mar 26, 2026

Leave a message

The issue you raised regarding troubleshooting an open circuit in a temperature-sensing cable is indeed critical to the timely response of a fire alarm system. I understand the urgency you feel when facing a sudden malfunction and needing to pinpoint the problem quickly; rapidly locating the break point is essential for minimizing safety risks.

When an open circuit occurs in a temperature-sensing cable, you can quickly troubleshoot the issue using a four-step method: "Signal Status Check → Segmented Resistance Measurement → Fault Location → Repair Verification." By combining the use of fault indicator lights, a multimeter, and the segmented isolation method, you can complete the preliminary localization and resolution of the issue within 30 minutes.

 

I. The Four-Step Rapid Troubleshooting Method

1. Check System Status and Fault Indications

Observe the Fire Alarm Control Panel: Does it report a "Fault" rather than a "Fire Alarm," and does it display a "Line Open" notification?

Check the Signal Processing Unit Indicators: If the yellow light (fault indicator) remains steadily lit, it indicates that an open circuit has been detected.

Verify Connections at the Terminal Box and Terminal Blocks: Check whether terminals such as LV1, LV3, etc., are loose or making poor contact.

This step helps rule out false alarms and confirms that a genuine open-circuit fault exists.

2. Measure Loop Resistance in Segments

Use a multimeter to perform resistance tests and determine the location of the open circuit:

Test Point

Normal Resistance Range

Abnormal Indication

Open-Circuit Test at Signal Processing Unit End

≥ 20 MΩ

Resistance reads infinity (∞) → Confirmed open circuit

Measurement at Terminal Box End

Same as above

If resistance here is normal, the break point lies within the intermediate cabling

Segmented Measurement at Intermediate Joints

Narrow down the scope segment by segment

If a specific segment reads ∞, that is where the break point is located

Operation Tip: Ensure the system power is disconnected before testing to avoid damaging the multimeter.

3. Locate the Break Point

Visual Inspection: Follow the cable's installation path to check for any signs of kinking, crushing under heavy objects, abrasion, or melting caused by high temperatures.

Segmented Isolation Method: Divide the long cable run into several segments; disconnect and measure each segment individually to narrow down the fault zone.

Use a Cable Fault Locator (Optional): Certain specialized devices can estimate the distance to the break point, thereby improving troubleshooting efficiency. 4. Repair and Verification

Rewiring: Cut away the damaged section, then restore the circuit using specialized connectors or by soldering; ensure proper insulation is applied.

System Reset: Reapply power to the system or briefly short-circuit the S1 reset pin; observe whether the green indicator light flashes (indicating normal operation).

Simulated Testing: Simulate a fire alarm or fault condition by applying heat or short-circuiting the S3 pins to verify that the alarm functionality has been restored.

 

II. Common Causes of Open Circuits and Preventive Measures

Cause

Manifestation

Preventive Measures

Forced Bending During Installation

Cable sheath rupture; internal conductor breakage

Avoid bending at sharp angles; use standard cable clips for secure fastening.

Compression by Heavy Objects

Local flattening; damage to the insulation layer

Route cables away from walkways and areas beneath heavy equipment.

Loose Wiring Terminals

Oxidation at contact points; unstable resistance readings

Conduct annual resistance testing to ensure a reading of ≥ 20 MΩ.

Aging Due to Excessive Heat

Cable becomes brittle and prone to breakage

Select heat-sensing cables with a temperature rating appropriate for the operating environment.

Maintenance Reminder: It is recommended to perform an "open-circuit resistance test" on the heat-sensing cable annually to detect potential hazards in a timely manner.