How to Reconfigure Parameters After Replacing an SRS1-T Module

Apr 16, 2026

Leave a message

After replacing an Omron SRS1-T module, there is no need to reconfigure any parameters. It is a purely hardware-based terminal resistor module designed for impedance matching at the physical layer; it involves no communication protocols or software configurations. Once correctly installed, communication will resume automatically.

 

1. Why is Parameter Configuration Unnecessary?

The SRS1-T is passive hardware: It does not store data or execute programs; it merely provides a 121Ω impedance at both ends of the bus to absorb signal reflections.

Functionality takes effect immediately: Provided the physical connections are correct (one module at the first station and one at the last), impedance matching occurs automatically upon power-up-no enabling, initialization, or "parameter writing" is required.

Non-intelligent module: Unlike PLCs or servo drives, the SRS1-T features no DIP switches, rotary selectors, or communication addresses; there are absolutely no configurable settings.

Tip: If communication anomalies occur after replacement, prioritize troubleshooting the installation location and resistance value rather than assuming that "parameters were not set."

 

2. Three Physical Connection Checks You Must Verify

Check Item

Correct Practice

Incorrect Example

Installation Location

Only at the two outermost nodes of the bus (the first and last stations)

Installed at intermediate slave stations as well

Resistance Verification

Equivalent resistance between A and B lines ≈ 60Ω (121Ω // 121Ω)

Measured value is 121Ω (only one end installed) or ∞ (no modules installed)

Shield Grounding

Shielding layer grounded at a single end (at the control room side)

Grounded at both ends, creating a ground loop that causes interference

Special Note: Some DeviceNet branch units (e.g., V624-DRT1) have built-in terminal resistors. If such a unit is already in use, there is no need to connect an external SRS1-T module, as doing so would result in redundant parallel connections and an excessively low resistance value.

 

3. Post-Replacement Verification Procedure

① Resistance Measurement (Power Off)

Shut down the system and cut power; use a multimeter to measure the resistance between lines A and B.

Normal Value: ≈60Ω (a fluctuation range of 58–63Ω is permissible).

② Waveform Analysis (Power On)

Connect an oscilloscope to observe the differential signal.

Normal Waveform: A clear square wave, free of ringing or overshoot.

③ Log Monitoring (System Operation)

Monitor the PLC/SCADA communication logs for a minimum of 4 hours.

Normal Behavior: No anomalies such as "Communication Timeout," "CRC Error," etc.

Acceptance Criteria: All three steps must be successfully passed to confirm that the replacement was successful.

info-1328-915

Send Inquiry
Contact usif have any question

You can either contact us via phone, email or online form below. Our specialist will contact you back shortly.

Contact now!