How to distinguish between fixed flange-mounted probe thermocouples and clamp-type thermocouples with movable threaded probe mounting

Mar 08, 2019

Leave a message

Structural Essence and Installation Mechanism Comparison

Fixed Flange Mounting Type: The probe end is welded or integrally formed with a rigid metal flange (such as a slip-on or weld-neck flange), and secured to the equipment flange interface with bolts, allowing for penetration into the medium. This forms a rigid, sealed, and non-adjustable installation structure.

Clamp-on Type: The probe is embedded in an elastic metal clamp ring, and the clamp bolt is tightened to make the probe conform to the outer surface of the pipe. This is a non-invasive, non-sealed, and non-adjustable surface contact type installation that does not require drilling holes. Adjustable Threaded Mounting Type: The outer wall of the probe protection tube is machined with standard external threads (such as M27×2, G3/4″), and installation is achieved by screwing it into the threaded interface reserved on the equipment. The insertion depth is adjustable, and some models support a replaceable sleeve design. This is an adjustable, medium-seal, non-penetrating insertion type installation.

 

Core Performance Parameter Three-Way Comparison

Performance Dimension

Fixed Flange Mounting Type

Clamp Type

Adjustable Threaded Mounting Type

Installation Method

Rigid connection with flange bolts, penetrating the medium

Clamp tightens the outer wall, surface contact

Threaded screw-in interface, adjustable insertion depth

Temperature Measurement Location

Inside the medium (steam, liquid, gas)

On the outer surface of the equipment

Inside the medium or near the wall (depending on insertion depth)

Temperature Range

0℃ to 1300℃+ (S/B/K type)

≤760℃ (limited by clamp material)

0℃ to 1300℃+ (matches the probe type)

Thermal Response Time

60–90 seconds

≤1–10 seconds

10–30 seconds (between the two, affected by insertion depth)

Sealing Capability

High sealing, resistant to PN40+ pressure, compliant with ASME B31.1

No sealing function

Medium sealing, relies on thread fit + sealing gasket, suitable for medium and low pressure (≤PN16)

Vibration Resistance

Very high (rigid connection)

Medium (easy to loosen)

Higher (threaded locking, better impact resistance than clamp)

Maintenance Convenience

Disassembly requires shutdown, loosening multiple bolts, high replacement cost

Quick online replacement, no shutdown required

Probe can be replaced online, sleeve can be retained, convenient maintenance

Calibratable

Removable for inspection, supports separate calibration

Not removable, entire unit replacement

Partially removable, supports separate probe calibration

Standard Basis

GB/T 30429-2013, GB/T 9119-2010 No national standard, manufacturer-defined according to IEC 60584-1 GB/T 30429-2013 (Assembled Thermocouple), JB/T 8622-1997 (Threaded Connection)

   

 

Application Scenarios and Selection Logic

Fixed Flange Type:

Suitable for temperature measurement inside high-pressure, high-temperature, and highly corrosive media: such as nuclear power main steam pipelines, hydrogenation reactors, refinery plant outlets, and large boiler flues;

Used for safety interlocks, mandatory calibration, and long-term continuous operation, requiring zero leakage and high reliability.

Hose Clamp Type:

Specifically used for external wall temperature measurement where drilling and welding are prohibited and quick inspection is required: such as injection molding machine screws, extruder barrels, heat treatment furnace rollers, water pipe outer walls, and lithium battery electrode pressing rollers;

Suitable for temporary monitoring, process temperature difference analysis, and multi-point deployment, requiring fast response and non-destructive installation.

Adjustable Threaded Type:

Suitable for pipeline temperature measurement in medium and low pressure environments, requiring precise control of insertion depth and high maintainability: such as chemical reactor side walls, pharmaceutical CIP pipelines, water treatment pipelines, and steam tracing pipes;

Used in scenarios requiring periodic calibration, probe replacement, and avoiding overall disassembly, balancing sealing performance and flexibility.

Selection Rhyme:

"For high-pressure media requiring penetration, choose flange; for quick external wall measurement without drilling, use hose clamp; for medium pressure, adjustable and maintainable applications, choose threaded." Consequences of Incorrect Selection:

Using a clamp-type sensor on high-pressure steam pipes → Temperature measurement failure, no seal, leakage risk;

Using a fixed flange on an injection molding machine screw → Damages equipment structure, doubles costs, impossible to maintain;

Using a movable threaded connection in an ultra-high pressure environment → Thread seal failure, media leakage, safety hazard.

 

Installation and Operation Guidelines

Fixed Flange Type:

Align the flange faces before installation, parallelism ≤ 0.1 mm/m;

Use a torque wrench to tighten the bolts diagonally and crosswise according to the standard torque (30–50 N·m);

Use metal-wound gaskets or graphite gaskets for sealing, rubber gaskets are prohibited;

Perform a leak test after installation, pressure ≥ 1.25 times the working pressure.

Clamp Type:

Clean the surface to be measured, remove oil and oxide layers, ensuring direct metal-to-metal contact;

Attach the probe to the surface, tighten the clamp bolts to ensure the probe is evenly pressed (recommended clamping force 5–10 N);

Do not use PTFE tape or adhesives, as they affect heat conduction;

Check the clamp tightness every two weeks to prevent poor contact due to thermal expansion and contraction.

Movable Threaded Type:

Clean the threaded interface, remove metal shavings and rust, ensuring smooth thread engagement;

Screw the probe to the preset depth (according to process requirements), and tighten moderately with a wrench (avoid overtightening to prevent thread stripping);

PTFE tape (1–2 turns) can be wrapped around the threads to enhance sealing, adhesives are prohibited;

Regularly check for loose threads, especially in environments with frequent starts and stops or vibrations;

When replacing the probe, only remove the probe body, retaining the threaded sleeve to reduce maintenance costs.